Skip to content

Eastron SDM

STABLE ETM CONSUMER

Connection: LOCAL

Connect Eastron SDM energy meters via Modbus RTU.

Eastron meters in the SDM range (SDM72, SDM120, SDM220, SDM230, SDM630) communicate over Modbus RTU on the hub's RS485 bus. Depending on the model they measure a single-phase or three-phase connection, and can be assigned one of three roles: root meter, consumption meter or production meter.

1. Hardware required

  • The Eastron meter (model according to the measurement need)
  • A USB↔RS485 adapter on the hub side
  • Bus cable, 2 twisted cores (A/B) + ground

2. RS485 wiring

Connect A↔A and B↔B between the adapter and the meter, with a common ground. Fit a 120 Ω termination resistor at each end of the bus.

To be confirmed on your bench

The meter's default baud rate and parity: confirm them in the device menu before commissioning.

3. Modbus addressing

Every device on the bus needs a unique slave address (set from the meter's menu). The default address is 1. If several Eastron meters share the bus, assign 1, 2, 3, …

4. Adding and configuring in the app

Devices are added from the app, in installer mode — see Adding a device. For the Eastron: discovery on the bus, model selection, then choice of role (root meter / consumption / production).

5. Verification

Once added, the connected state turns true and the quantities (currentPower and so on) start updating. If no data arrives: check the A/B wiring, the slave address and the termination.


Reference

Application labels

The keys and labels below are the ones the application shows, in English. They are left verbatim so that you find them word for word on screen.

Manufacturer: Eastron
Plugin: eastron

Supported models

Model Role Transport Pairing Quantities
Compteur réseau — Eastron SDM630 (3φ) Energy meter Modbus RTU Auto-discovery 20
Consommateur (PAC/charge) — Eastron SDM630 (3φ) Consumption meter Modbus RTU Auto-discovery 4
Onduleur / PV — Eastron SDM630 (3φ) Production meter Modbus RTU Auto-discovery 4
Compteur réseau — Eastron SDM72 (3φ) Energy meter Modbus RTU Auto-discovery 14
Consommateur (PAC/charge) — Eastron SDM72 (3φ) Consumption meter Modbus RTU Auto-discovery 4
Onduleur / PV — Eastron SDM72 (3φ) Production meter Modbus RTU Auto-discovery 4
Compteur réseau — Eastron SDM120 (1φ) Energy meter Modbus RTU Auto-discovery 7
Consommateur (PAC/charge) — Eastron SDM120 (1φ) Consumption meter Modbus RTU Auto-discovery 4
Onduleur / PV — Eastron SDM120 (1φ) Production meter Modbus RTU Auto-discovery 4
Compteur réseau — Eastron SDM220 (1φ) Energy meter Modbus RTU Auto-discovery 7
Consommateur (PAC/charge) — Eastron SDM220 (1φ) Consumption meter Modbus RTU Auto-discovery 4
Onduleur / PV — Eastron SDM220 (1φ) Production meter Modbus RTU Auto-discovery 4
Compteur réseau — Eastron SDM230 (1φ) Energy meter Modbus RTU Auto-discovery 7
Consommateur (PAC/charge) — Eastron SDM230 (1φ) Consumption meter Modbus RTU Auto-discovery 4
Onduleur / PV — Eastron SDM230 (1φ) Production meter Modbus RTU Auto-discovery 4

Per-model detail

Compteur réseau — Eastron SDM630 (3φ) — sdm630

Discovery parameters:

Key Label Type Range Default
slaveAddress Slave address int — 1

Settings:

Key Label Type Range Default Read-only
slaveAddress Modbus slave address uint — 1 no
modbusMasterUuid Modbus RTU master QUuid — — yes

Measured quantities:

Key Quantity Type Unit
connected Connected bool —
voltagePhaseA Voltage phase A double Volt
voltagePhaseB Voltage phase B double Volt
voltagePhaseC Voltage phase C double Volt
currentPhaseA Current phase A double Ampere
currentPhaseB Current phase B double Ampere
currentPhaseC Current phase C double Ampere
currentPower Current power double Watt
currentPowerPhaseA Current power phase A double Watt
currentPowerPhaseB Current power phase B double Watt
currentPowerPhaseC Current power phase C double Watt
frequency Frequency double Hertz
totalEnergyConsumed Total energy consumed double KiloWattHour
totalEnergyProduced Total energy produced double KiloWattHour
energyConsumedPhaseA Energy consumed phase A double KiloWattHour
energyConsumedPhaseB Energy consumed phase B double KiloWattHour
energyConsumedPhaseC Energy consumed phase C double KiloWattHour
energyProducedPhaseA Energy produced phase A double KiloWattHour
energyProducedPhaseB Energy produced phase B double KiloWattHour
energyProducedPhaseC Energy produced phase C double KiloWattHour
Consommateur (PAC/charge) — Eastron SDM630 (3φ) — sdm630Consumer

Discovery parameters:

Key Label Type Range Default
slaveAddress Slave address int — 1

Settings:

Key Label Type Range Default Read-only
slaveAddress Modbus slave address uint — 1 no
modbusMasterUuid Modbus RTU master QUuid — — yes

Measured quantities:

Key Quantity Type Unit
connected Connected bool —
currentPower Current power double Watt
totalEnergyConsumed Total energy consumed double KiloWattHour
frequency Frequency double Hertz
Onduleur / PV — Eastron SDM630 (3φ) — sdm630Producer

Discovery parameters:

Key Label Type Range Default
slaveAddress Slave address int — 1

Settings:

Key Label Type Range Default Read-only
slaveAddress Modbus slave address uint — 1 no
modbusMasterUuid Modbus RTU master QUuid — — yes

Measured quantities:

Key Quantity Type Unit
connected Connected bool —
currentPower Current power double Watt
totalEnergyProduced Total energy produced double KiloWattHour
frequency Frequency double Hertz
Compteur réseau — Eastron SDM72 (3φ) — sdm72

Discovery parameters:

Key Label Type Range Default
slaveAddress Slave address int — 1

Settings:

Key Label Type Range Default Read-only
slaveAddress Modbus slave address uint — 1 no
modbusMasterUuid Modbus RTU master QUuid — — yes

Measured quantities:

Key Quantity Type Unit
connected Connected bool —
voltagePhaseA Voltage phase A double Volt
voltagePhaseB Voltage phase B double Volt
voltagePhaseC Voltage phase C double Volt
currentPhaseA Current phase A double Ampere
currentPhaseB Current phase B double Ampere
currentPhaseC Current phase C double Ampere
currentPower Current power double Watt
currentPowerPhaseA Current power phase A double Watt
currentPowerPhaseB Current power phase B double Watt
currentPowerPhaseC Current power phase C double Watt
frequency Frequency double Hertz
totalEnergyConsumed Total energy consumed double KiloWattHour
totalEnergyProduced Total energy produced double KiloWattHour
Consommateur (PAC/charge) — Eastron SDM72 (3φ) — sdm72Consumer

Discovery parameters:

Key Label Type Range Default
slaveAddress Slave address int — 1

Settings:

Key Label Type Range Default Read-only
slaveAddress Modbus slave address uint — 1 no
modbusMasterUuid Modbus RTU master QUuid — — yes

Measured quantities:

Key Quantity Type Unit
connected Connected bool —
currentPower Current power double Watt
totalEnergyConsumed Total energy consumed double KiloWattHour
frequency Frequency double Hertz
Onduleur / PV — Eastron SDM72 (3φ) — sdm72Producer

Discovery parameters:

Key Label Type Range Default
slaveAddress Slave address int — 1

Settings:

Key Label Type Range Default Read-only
slaveAddress Modbus slave address uint — 1 no
modbusMasterUuid Modbus RTU master QUuid — — yes

Measured quantities:

Key Quantity Type Unit
connected Connected bool —
currentPower Current power double Watt
totalEnergyProduced Total energy produced double KiloWattHour
frequency Frequency double Hertz
Compteur réseau — Eastron SDM120 (1φ) — sdm120

Discovery parameters:

Key Label Type Range Default
slaveAddress Slave address int — 1

Settings:

Key Label Type Range Default Read-only
slaveAddress Modbus slave address uint — 1 no
modbusMasterUuid Modbus RTU master QUuid — — yes

Measured quantities:

Key Quantity Type Unit
connected Connected bool —
voltagePhaseA Voltage double Volt
currentPhaseA Current double Ampere
currentPower Current power double Watt
frequency Frequency double Hertz
totalEnergyConsumed Total energy consumed double KiloWattHour
totalEnergyProduced Total energy produced double KiloWattHour
Consommateur (PAC/charge) — Eastron SDM120 (1φ) — sdm120Consumer

Discovery parameters:

Key Label Type Range Default
slaveAddress Slave address int — 1

Settings:

Key Label Type Range Default Read-only
slaveAddress Modbus slave address uint — 1 no
modbusMasterUuid Modbus RTU master QUuid — — yes

Measured quantities:

Key Quantity Type Unit
connected Connected bool —
currentPower Current power double Watt
totalEnergyConsumed Total energy consumed double KiloWattHour
frequency Frequency double Hertz
Onduleur / PV — Eastron SDM120 (1φ) — sdm120Producer

Discovery parameters:

Key Label Type Range Default
slaveAddress Slave address int — 1

Settings:

Key Label Type Range Default Read-only
slaveAddress Modbus slave address uint — 1 no
modbusMasterUuid Modbus RTU master QUuid — — yes

Measured quantities:

Key Quantity Type Unit
connected Connected bool —
currentPower Current power double Watt
totalEnergyProduced Total energy produced double KiloWattHour
frequency Frequency double Hertz
Compteur réseau — Eastron SDM220 (1φ) — sdm220

Discovery parameters:

Key Label Type Range Default
slaveAddress Slave address int — 1

Settings:

Key Label Type Range Default Read-only
slaveAddress Modbus slave address uint — 1 no
modbusMasterUuid Modbus RTU master QUuid — — yes

Measured quantities:

Key Quantity Type Unit
connected Connected bool —
voltagePhaseA Voltage double Volt
currentPhaseA Current double Ampere
currentPower Current power double Watt
frequency Frequency double Hertz
totalEnergyConsumed Total energy consumed double KiloWattHour
totalEnergyProduced Total energy produced double KiloWattHour
Consommateur (PAC/charge) — Eastron SDM220 (1φ) — sdm220Consumer

Discovery parameters:

Key Label Type Range Default
slaveAddress Slave address int — 1

Settings:

Key Label Type Range Default Read-only
slaveAddress Modbus slave address uint — 1 no
modbusMasterUuid Modbus RTU master QUuid — — yes

Measured quantities:

Key Quantity Type Unit
connected Connected bool —
currentPower Current power double Watt
totalEnergyConsumed Total energy consumed double KiloWattHour
frequency Frequency double Hertz
Onduleur / PV — Eastron SDM220 (1φ) — sdm220Producer

Discovery parameters:

Key Label Type Range Default
slaveAddress Slave address int — 1

Settings:

Key Label Type Range Default Read-only
slaveAddress Modbus slave address uint — 1 no
modbusMasterUuid Modbus RTU master QUuid — — yes

Measured quantities:

Key Quantity Type Unit
connected Connected bool —
currentPower Current power double Watt
totalEnergyProduced Total energy produced double KiloWattHour
frequency Frequency double Hertz
Compteur réseau — Eastron SDM230 (1φ) — sdm230

Discovery parameters:

Key Label Type Range Default
slaveAddress Slave address int — 1

Settings:

Key Label Type Range Default Read-only
slaveAddress Modbus slave address uint — 1 no
modbusMasterUuid Modbus RTU master QUuid — — yes

Measured quantities:

Key Quantity Type Unit
connected Connected bool —
voltagePhaseA Voltage double Volt
currentPhaseA Current double Ampere
currentPower Current power double Watt
frequency Frequency double Hertz
totalEnergyConsumed Total energy consumed double KiloWattHour
totalEnergyProduced Total energy produced double KiloWattHour
Consommateur (PAC/charge) — Eastron SDM230 (1φ) — sdm230Consumer

Discovery parameters:

Key Label Type Range Default
slaveAddress Slave address int — 1

Settings:

Key Label Type Range Default Read-only
slaveAddress Modbus slave address uint — 1 no
modbusMasterUuid Modbus RTU master QUuid — — yes

Measured quantities:

Key Quantity Type Unit
connected Connected bool —
currentPower Current power double Watt
totalEnergyConsumed Total energy consumed double KiloWattHour
frequency Frequency double Hertz
Onduleur / PV — Eastron SDM230 (1φ) — sdm230Producer

Discovery parameters:

Key Label Type Range Default
slaveAddress Slave address int — 1

Settings:

Key Label Type Range Default Read-only
slaveAddress Modbus slave address uint — 1 no
modbusMasterUuid Modbus RTU master QUuid — — yes

Measured quantities:

Key Quantity Type Unit
connected Connected bool —
currentPower Current power double Watt
totalEnergyProduced Total energy produced double KiloWattHour
frequency Frequency double Hertz