ABB B2x meter¶
TESTING ETM
Connection: LOCAL
Connect ABB B21 / B23 / B24 energy meters via Modbus RTU.
The ABB B2x energy meter communicates over Modbus RTU on the hub's RS485 bus. Three-phase measurement (voltages, currents and power per phase).
1. Hardware required¶
- An ABB B2x meter
- A USB↔RS485 adapter on the hub side
- Bus cable, 2 cores (A/B) + ground
2. RS485 wiring¶
A↔A, B↔B, common ground, 120 Ω at the end of the bus.
3. Modbus addressing¶
A unique slave address on the bus (1–254, default 1).
4. Adding in PowerSync¶
Added by automatic discovery or manually (entering the slave address). See Adding a device.
Reference¶
Application labels
The keys and labels below are the ones the application shows, in English. They are left verbatim so that you find them word for word on screen.
Manufacturer: ABB
Plugin: AbbB2x
Supported models¶
| Model | Role | Transport | Pairing | Quantities |
|---|---|---|---|---|
| ABB B2x energy meter | Energy meter | Modbus RTU | Auto-discovery / Manual | 14 |
Per-model detail¶
ABB B2x energy meter — abbB2x
Discovery parameters:
| Key | Label | Type | Range | Default |
|---|---|---|---|---|
slaveAddress |
Modbus slave address | uint | 1–254 | 1 |
Settings:
| Key | Label | Type | Range | Default | Read-only |
|---|---|---|---|---|---|
slaveAddress |
Modbus slave address | uint | 1–254 | 1 |
yes |
modbusMasterUuid |
Modbus RTU master | QString | — | — | yes |
Measured quantities:
| Key | Quantity | Type | Unit |
|---|---|---|---|
connected |
Connected | bool | — |
currentPower |
Current power | double | Watt |
totalEnergyConsumed |
Total energy consumed | double | KiloWattHour |
totalEnergyProduced |
Total energy produced | double | KiloWattHour |
frequency |
Frequency | double | Hertz |
voltagePhaseA |
Voltage phase A | double | Volt |
voltagePhaseB |
Voltage phase B | double | Volt |
voltagePhaseC |
Voltage phase C | double | Volt |
currentPhaseA |
Current phase A | double | Ampere |
currentPhaseB |
Current phase B | double | Ampere |
currentPhaseC |
Current phase C | double | Ampere |
currentPowerPhaseA |
Current power phase A | double | Watt |
currentPowerPhaseB |
Current power phase B | double | Watt |
currentPowerPhaseC |
Current power phase C | double | Watt |