Aller au contenu

alpha innotec

NIGHTLY NYMEA COMMUNITY

Integrate alpha innotec heat pumps into nymea.

Fabricant : alpha Innotec
Plugin : AlphaInnotec

Modèles pris en charge

Modèle Rôle Transport Ajout Grandeurs
alpha connect smartgridheatpump Modbus TCP Découverte automatique / Ajout manuel 27

Détail par modèle

alpha connect — alphaConnect

Réglages :

Clé Libellé Type Plage Défaut Lecture seule
address IP address QString non
hostName Host name QString non
macAddress MAC address QString non
port Port int 502 non
slaveId Modbus slave ID int 1 non

Grandeurs mesurées :

Clé Grandeur Type Unité
connected Connected bool
heatingOn Heating on bool
coolingOn Cooling on bool
flowTemperature Flow temperature double DegreeCelsius
returnTemperature Return temperature double DegreeCelsius
externalReturnTemperature External return temperature double DegreeCelsius
hotWaterTemperature Hot water temperature double DegreeCelsius
hotGasTemperature Hot gas temperature double DegreeCelsius
heatSourceInletTemperature Heat source inlet temperature double DegreeCelsius
heatSourceOutletTemperature Heat source outlet temperature double DegreeCelsius
roomTemperature1 Room remote adjuster 1 temperature double DegreeCelsius
roomTemperature2 Room remote adjuster 2 temperature double DegreeCelsius
roomTemperature3 Room remote adjuster 3 temperature double DegreeCelsius
solarCollectorTemperature Solar collector temperature double DegreeCelsius
solarStorageTankTemperature Solar storage tank temperature double DegreeCelsius
externalEnergySourceTemperature External energy source temperature double DegreeCelsius
supplyAirTemperature Supply air temperature double DegreeCelsius
externalAirTemperature External air temperature double DegreeCelsius
systemStatus System status QString
heatingPumpOperatingHours Heating pump operating hours uint Hours
outdoorTemperature Outdoor temperature double DegreeCelsius
returnSetpointTemperature Return temperature setpoint double DegreeCelsius
hotWaterSetpointTemperature Hot water temperature setpoint double DegreeCelsius
sgReadyMode Smart grid mode QString
totalEnergy Total energy double KiloWattHour
heatingEnergy Heating energy double KiloWattHour
hotWaterEnergy Hot water energy double KiloWattHour